The rising
edge the input signal evaluated and extended value that can be
selected from the menu.Page 133
Detailed description REG-DP/ REG-DPA parameters
0 Binary inputs
The following input functions (BIFs) can allocated the physical inputs either WinEDC
or directly the REG-DP/ REG-DPA:
Allocating binary input functions WinEDC Allocating binary input functions the
REG-DP/ REG-DPA
Key sequence:
<MENU><F3><F3><F1><F2><F2>
Table 7-1: Parameterization options for binary inputs
No.g. The standard regu-
lation process does not use this input. Only possible MAN mode!
6 Mot_Run P-coil regulator: The running message transmitted for the statistical
unit. The rising
edge the input signal evaluated and extended value that can be
selected from the menu. Name Function
0 OFF: The input not allocated input function.
1 PROG The input only allocated the background program. Motor runs long as
the signal occurs. This enables motor runtimes recorded that are not caused by
the regulator, e.
7 End_H P-coil regulator: 'End position Higher' reached
8 End_L P-coil regulator: 'End position Lower' reached
9 E:Man P-coil regulator: Currently works only BOF41: E:Man passed no
function defined!
.
2 Motor_H Signal regulator: Adjust P-coil direction 'Higher'. The signals are virtually sent
out into the air. Only possible MAN mode!
3 Motor_L Signal regulator: Adjust P-coil direction 'Lower'. Only possible MAN mode!
5 Imp_Mot_L Impulse signal regulator: Adjust P-coil direction 'Lower'. Only possible MAN mode!
4 Imp_Mot_H Impulse signal regulator: Adjust P-coil direction 'Higher'., adjusting the P-coil site. Motor runs long as
the signal occurs