Default setting: min Parameter Locking (at Umin) If Une Umin not found across the P-coil's whole adjustment range, the P-coil adjusted to the parameterized end position.Page 115 Detailed description REG-DP/ REG-DPA parameters 0 100 10 -2 10 -1 10 0 10 1 Coilposition Ipos % Une % ICE_max v Uearth-threshold Umax-threshold Umax-end Figure 82: Adjustable limit value for the regulation the P-Coil Parameter New search after If the zero sequence voltage Une stays smaller than the threshold value Umin during the whole time, new search for the resonance point will start automatically when this time has lapsed. On symmetrical cable networks with big detuning, switching operation may only achieve a small voltage change. The regulator must switched back AUTO mode either manually or through the SCADA system. Default setting: OFF: . This automatic search ensures that unidentified switching opera- tion that was performed after this time correctly tuned. locking enabled, the regulator switched MAN and stays this mode