Default setting: min
Parameter Locking (at Umin)
If Une Umin not found across the P-coil's whole adjustment range, the P-coil adjusted to
the parameterized end position.Page 115
Detailed description REG-DP/ REG-DPA parameters
0 100
10
-2
10
-1
10
0
10
1
Coilposition Ipos %
Une %
ICE_max
v
Uearth-threshold
Umax-threshold
Umax-end
Figure 82: Adjustable limit value for the regulation the P-Coil
Parameter New search after
If the zero sequence voltage Une stays smaller than the threshold value Umin during the
whole time, new search for the resonance point will start automatically when this time
has lapsed.
On symmetrical cable networks with big detuning, switching operation may only achieve
a small voltage change. The regulator must switched back AUTO mode either manually or
through the SCADA system.
Default setting: OFF:
. This automatic search ensures that unidentified switching opera-
tion that was performed after this time correctly tuned. locking enabled, the regulator switched MAN and
stays this mode