Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 114 z 272

Jak získat tento dokument?






Poznámky redaktora
.Page 114 Detailed description REG-DP/ REG-DPA parameters We take care it. Default setting: min Figure shows the combination and description the above-mentioned parameters. This frequently caused the transformer P-coil being temporarily switched off during grid switching. the zero sequence voltage Une Umin. Only then are the measured data accepted for the determination the resonance curve. valid estimate cannot made, the P-coil is adjusted waiting position based the parameterization. Default setting: 0.2% Parameter end position (at Umin) In order calculate and estimate the resonance curve, least one measurement point must bigger than the set Umin threshold. Parameter Message delay (at Umin) The message delay parameter sets the delay for the Umin message. This waiting position can be: 0 Standby position or 0 Tuning point (resonance point including the compensation that was set the last calculation) Default setting: Tuning point A new search process starts if 0 the zero sequence voltage Une leaves the tolerance range or 0 the regulator set perform cyclical control the resonance point. the P-coil not reconnected the grid after the switch, there will not be enough zero sequence voltage for the regulation and the regulator will display message. search not start- ed within this time, the message 'Une Umin' triggered