Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 114 z 272

Jak získat tento dokument?






Poznámky redaktora
2% Parameter end position (at Umin) In order calculate and estimate the resonance curve, least one measurement point must bigger than the set Umin threshold. the zero sequence voltage Une Umin. This frequently caused the transformer P-coil being temporarily switched off during grid switching. Parameter Message delay (at Umin) The message delay parameter sets the delay for the Umin message. Default setting: 0. This waiting position can be: 0 Standby position or 0 Tuning point (resonance point including the compensation that was set the last calculation) Default setting: Tuning point A new search process starts if 0 the zero sequence voltage Une leaves the tolerance range or 0 the regulator set perform cyclical control the resonance point. valid estimate cannot made, the P-coil is adjusted waiting position based the parameterization. the P-coil not reconnected the grid after the switch, there will not be enough zero sequence voltage for the regulation and the regulator will display message.Page 114 Detailed description REG-DP/ REG-DPA parameters We take care it. . Only then are the measured data accepted for the determination the resonance curve. search not start- ed within this time, the message 'Une Umin' triggered. Default setting: min Figure shows the combination and description the above-mentioned parameters