Poznámky redaktora
8 (Resistor Braking Unit Internal Resistor)
2.
- Actual feedbacks: ready/running, current/
voltage/power etc.3 (Braking Chopper Unit External Resistor)
Hardware
Optional inverter output isolator
Optional customer signal I/Os
Varnished control boards
Mechanics
Vibration dampers
Maritime handgrips for doors
Anticondensation heaters
Locking device for 90° open doors
Flame-retardant properties
Halogen-free wiring and cable ducts
Redundancy
Various redundancy schemes
(please contact ABB for further information)
17 ACS 6000 ABB
.0 3.3 kV
Optional: 2.
• Braking chopper
Maritime properties
Marine standards
IEC 60092, IEC 60721-3-6, IEC 60068-2-
(1,2,6,30,52)
CE marking according directives
Marine certification
Available for Lloyd’s, DNV, ABS and others
Braking
0.3 kV
Ambient temperature
+5 (higher with derating)
31 113 (higher with derating)
Enclosure classes
Standard: IP32
Optional: IP54
Control interface (optional)
All common fieldbuses including Profibus,
Modbus, DeviceNet, ABB AF100, others
Industrial'7 Compatible (Level 1)
Protective functions
Converter:
Overcurrent, short circuit, earth fault,
phase loss, overvoltage, undervoltage, over
temperature, output frequency, network
disturbance, cooling supervision
Motor:
Overload, underload, stall protection
Optional
• Motor supervision I/Os
- Fault/alarm: overtemperature, vibration of
bearings
- 100: winding bearing temperatures
• Transformer supervision I/Os
- Fault/alarm: overtemperature, overcurrent
- 100: winding temperatures
• Hardwired signals: drive control and drive
status indication
- References: start/stop, speed/torque etc. Alternatively the drive can be
equipped with back-up capacitors (for short
term control power-loss ride-through)
Output frequency
0 ±75 (Twin 250 Hz)
Rated output voltage
Standard: 3.Data sheet ACS 6000
General features
Inverter type
Voltage Source Inverter Neutral-Point Clamped
(VSI-NPC)
Motors
Induction, synchronous and permanent magnet
motors; 3000 000 kVA water cooled
Standards
IEC 60146, IEC 60721
All common standards including EN, IEC, CE
Marine standards optional
Input
Medium voltage input transformer for 12-pulse
diode rectifier, 6-pulse ARU
Variation: ±10 nominal voltage, down to
-25 safe operation with derated
output
Auxiliary voltage
Common 400 690 VAC, 3-phase,
50 Hz/60 Hz
UPS (Uninterruptable Power Supply)
If available, UPS can connected for control
power supply, 110-240 VAC, single phase or
110/220 VDC