Poznámky redaktora
The ission limits are com parable according the
following table, EMC standards.
Selecting EMC filter
The following table gives the correct filter selection.2009
. also
includes establishments directly connected without
interm ediate transform low -voltage pow er
supply netw ork hich supplies buildings used for
dom estic purposes. The ACS800
is designed have adequate immunity against
interference from other equipment. This called immunity. Each ACS800 model can equipped with
an inbuilt filter reduce high frequency emission.
EN 61800-3/A11 (2000),
product standard
EN 61800-3 (2004),
product standard
EN 55011, product family
standard for industrial, scientific
and medical (ISM) equipment
EN 61000-6-4, generic emission
standard for
industrial environments
EN 61000-6-3, generic emission
standard for residential,
commercial and light-industrial
environment
1st environment, unrestricted distribution Category Group Class Not applicable Applicable
1st environment, restricted distribution Category Group Class Applicable Not applicable
2ndenvironment, unrestricted distribution Category Group Class Not applicable Not applicable
2ndenvironment, restricted distribution Category Not applicable Not applicable Not applicable
Type Voltage Frame
sizes
1st environment, restricted distribution, C2,
grounded network (TN)
2ndenvironment, C3, grounded
network (TN)
2ndenvironment, C3, floating
network (IT)
ACS800-01
400-500 R2-R6 +E202 +E200 /+E210 (R6 frame size) /+E210 (R6 frame size)
690 R2-R6 +E200 /+E210 (R6 frame size) /+E210 (R6 frame size)
ACS800-11
400-500 R5-R6 +E202 +E200 *)
690 +E200 *)
ACS800-31
400-500 R5-R6 +E202 +E200 *)
690 +E200 *)
ACS800-02
400-500 R7-R8 +E202 +E210 +E210
690 R7-R8 +E210 +E210
ACS800-07
400-500
R5-R8 +E202 +E210 +E200 (R5 frame size) +E210
nxR8i +E202 (up 1000A) standard standard
690
R5-R8 +E210 +E200 (R5 frame size) +E210
nxR8i standard standard
ACS880-07LC
400-500 nxR8i +E202 (up 1000A) standard standard
690 nxR8i standard standard
ACS800-17
400-500
R6 +E202 +E200 *)
R7i-nxR8i +E202 (up 1000 standard standard
690 R7i-nxR8i standard standard
ACS800-37
400-500
R6 +E202 +E200 *)
R7i-nxR8i +E202 (up 1000 standard standard
690 R7i-nxR8i standard standard
*) These drives are category equipment and plan for installation required. Drive
units complying with requirements 61800-3 are
compliant with com parable categories 55011
and 61000-6-3/4, but not necessarily vice versa. This called
EM sta s
emission.
EMC standards
The EMC product standard (EN 61800-3 (2004)) covers
the specific EMC requirements stated for drives (tested
with motor and cable) within the EU.”
EMC Electromagnetic compatibility and
ACS800
The electrical/electronic equipm ent must able to
operate without problems within electromagnetic
environment. Likewise, the
equipm ent must not disturb interfere with any other
product system within its locality.
All declarations concerning marking can found
on the www.EMC filters
1st environment 2ndenvironment
1stenvironment
“1st environment includes domestic premises.
EMC standards such 55011, 61000-6-3/4,
are applicable industrial and domestic equipments
and systems including drive com ponent inside.”
2ndenvironment
“2nd environment includes all establishments other
than those directly connected low voltage power
supply network hich supplies buildings used for
domestic purposes.
EN 55011 and 61000-6-3/4 not specify cable
length nor require motor connected load.2.abb.
38 Hardware options 68375126 REV 17.com/drives website