Poznámky redaktora
- Status feedback signals: ready/running
- Analog signals: current/voltage/power etc.96 (Total: >0.9 kV
Optional: 4.95)
17 ACS 5000 ABB
.0 6.5 (incl.Data sheet ACS 5000
Inverter type
Voltage Source Inverter Multilevel-Fuseless
(VSI-MF),
9 levels line-to-line, with fast-switching power
semiconductors Integrated Gate Commu
tated Thyristors (IGCTs), without parallel or
series connected devices
Motors
Induction, synchronous and permanent magnet
motors; 2000 7000 kVA air cooled
5000 22000 kVA water cooled
Standards
All common standards including EN, IEC, CE
Ambient temperature
+ (higher with derating)
34 104 (higher with derating)
Enclosure classes
Standard: IP21 air cooled
IP32 water cooled
Optional: IP42 air cooled
up IP54 water cooled
Control interface (optional)
All common fieldbuses including Profibus,
Modbus, DeviceNet, ABB AF100, others
Industrial17 Compatible (Level 1)
Input
Medium voltage input transformer for 36-pulse
diode rectifier
Variation: ±10 nominal voltage, down to
-25 safe operation with derated
output
Auxiliary voltage
Common 400 480 VAC, 3-phase,
50 Hz/60 Hz, (up 690 VAC for water cooled
drives)
UPS (Uninterruptable Power Supply)
If available, UPS can connected for control
power supply, 110 240 VAC, single phase or
110/220 VDC. Alternatively the drive can be
equipped with back-up capacitors (for short
term control power-loss ride-through)
Output frequency
0 ±75 Hz, ±250 optional
(higher request)
Rated output voltage
Standard: 6.9 kV, Hz/60 Hz
- kV, Hz/60 Hz
Input power factor
Fundamental: >0.16 kV
Efficiency converter
Typically >98. auxiliaries)
Protective functions
Converter:
Overcurrent, short circuit, earth fault,
phase loss, overvoltage, undervoltage, over
temperature, output frequency, network
disturbance, cooling supervision
Motor:
Overload, underload, stall protection
Optional
• Motor supervision I/Os
- Fault/alarm: overtemperature, vibration of
bearings
- 100: winding bearing temperatures
• Transformer supervision I/Os
- Fault/alarm: overtemperature, Buchholz
- 100: winding temperatures
• Hardwired signals for remote drive control
- References: start/stop, speed/torque etc.
• Redundant cooling fans for air-cooled drives
• Synchronous bypass functionality
(for starting six motors)
• Integrated transformer, input voltage range:
- 6