Filter selection table for ACS800
Motor type Nominal mains Motor insulation requirement
vo|tage (UJ
ABB and 500 Standard insulation system.3 ps, du/dt filtering not required.
U Peak line line voltage motor terminals.
HXR and motors du/dt filtering with voltages over 500 V.
600 690 Reinforced insulation system conjunction with du/dt filtering.2.
At Rise time, i.
Non-ABB 420 Insulation system must withstand Ull=1300 V.2 ps, du/dt filtering not required. Additionally, du/dt filtering reduces
capacitive leakage currents and high frequency
emission the otor cable well high frequency
losses and bearing currents the motor.
500 600 the insulation system withstands Ull=1800 du/dt filtering not required.35 times the mains network voltage
with very short rise time. The voltage can almost
double the otor terminals, depending otor
cable properties.
With du/dt filtering, the insulation system must withstand Ull=1600 V.
Symbol Explanation
Un Nominal mains voltage.e.
With du/dt filtering, the insulation system must withstand Ûll=1300 V.
With du/dt filtering, the insulation system must withstand Ûll=1800 V.Du/dt filters
As with all frequency converters employing the most
m odern inverter technology, the ACS800 output
comprises regardless output frequency pulses of
approximately 1.
3AFE68248531 REV 20.2009 Hardware options 29
.
M3 motors 500 600 Standard insulation system conjunction with du/dt filtering reinforced insulation.
W hen needed? The need for du/dt filtering
depends the motor insulation.
ABB form-wound 380 690 Standard insulation system. For
more information see the ACS800 hardware manuals.
HXR and motors
ABB random-wound 380 690 Check motor insulation system with the motor manufacturer.
Insulated N-end (non-driven end) bearings and or
com ode filters are also required for motor
bearing currents with motors bigger than 100 kW. interval during which line line voltage motor terminals changes from 10% 90% full voltage range.
600 690 the motor insulation system withstands Ull=2000 and At=0.
Random-wound and
Form-wound
420 500 the insulation system withstands Ull=1600 and At=0.
Du/dt filtering suppresses inverter output voltage
spikes and rapid voltage changes that stress otor
insulation. the motor does not fulfil the following
requirements, the lifetime the motor might shorten. For information on
the construction the motor insulation, consult the
manufacturer