Frekvenční měniče Katalogy, manuály (EN+CZ)

| Kategorie: Katalog  | Tento dokument chci!

Vydal: ABB s.r.o, ELSYNN Autor: ABB ELSYnn

Strana 63 z 825







Poznámky redaktora
3 ^s, du /dt filtering not required.2004 25 . A Rise tim i. As with all frequency converters employing the most modern IGBT inverter technology, the ACS800 output comprises regardless output frequency pulses of approximately 1. .e. 500 600 Standard insulation system conjunction with du/dt filtering reinforced insulation. U Peak line line voltage otor term inals. the motor does not fulfil the following requirements, the lifetime the motor might shorten.3. Filter selection table for ACS800 M otor type Nominal mains voltage (Un) M otor insulation requirem ent ABB and M3 otors Un 500 Standard insulation system. ABB random -wound HXR and otors 380 690 Check otor insulation system ith the otor manufacturer. 600 690 Reinforced insulation system conjunction ith /dt filtering.2 ^s, du/dt filtering is not required. 600 690 the otor insulation system ithstands ÛLL=1800 du/dt filtering not required. When needed? The need for du/dt filtering de­ pends the motor insulation. For more information see the ACS800 hardware manuals. With du/dt filtering, the insulation system must withstand ÛLL=1300 V. interval during hich line line voltage otor term inals changes from 10% 90% of full voltage range. 420 500 the insulation system ithstands ÛLL=1600 and At=0. ABB form ound HXR and otors 380 690 Standard insulation system. The voltage can almost double the motor terminals, depending motor cable properties. 3AFE 68248531 REV 31. W ith /dt filtering, the insulation system must ithstand ÛLL=1600 V. 500 600 the insulation system ithstands ÛLL=1800 /dt filtering not required. Du/dt filtering suppresses inverter output voltage spikes and rapid voltage changes that stress motor insulation. Additionally, du/dt filtering reduces capaci­ tive leakage currents and high frequency emission of the motor cable well high frequency losses and bearing currents the motor. For information the construction the motor insulation, consult the manufacturer. du /dt filtering with voltages over 500 V. Non-ABB Form -wound 600 690 the otor insulation system ithstands ÛLL=2000 and At=0. Insulated N-end (non-driven end) bearings and or common mode filters are also required for motor bearing currents with motors bigger than 100 kW.Output filters Factory installed filters.35 times the mains network voltage with very short rise time. Sym bol Explanation Un Nominal ains voltage. N on-ABB R andom ound Un 420 Insulation system must ithstand ÛLL=1300 V