Poznámky redaktora
HXR and motors
ABB random -wound 380 690 heck otor insulation system with the otor manufacturer. ith du/dt filtering, the insulation system must withstand LL=1300 V.
HXR and motors du/dt filtering with voltages over 500 V.du/dt filters
Du/dt filtering suppresses inverter output voltage spikes
and rapid voltage changes that stress motor insulation. the
motor does not fulfil the following requirements, the
lifetime the motor might decrease.
42 Hardware options FE68404592 REV 3.
Random -wound and
Form -wound
420 500 the insulation system withstands LL=1600 and At=0.
600 690 the motor insulation system withstands LL=2000 and At=0.e.
ABB form -wound 380 690 Standard insulation system.
Additionally, du/dt filtering reduces capacitive leakage
currents and high frequency emission the motor
cable well high frequency losses and bearing
currents the motor.
The need for du/dt filtering depends the motor
insulation.2009
.3 ^s,
du/dt filtering not required.
M otor type Nominal mains
voltage (UN)
M otor insulation requirement
ABB and 500 Standard insulation system.
600 690 Reinforced insulation system conjunction with du/dt filtering. For
m ore information please see the ACS800 hardware
manuals.
At Rise tim i.
Û Peak line line voltage otor terminals. interval during which line line voltage otor term inals changes from 10% 90% of
full voltage range. ith du/dt filtering, the insulation system must
w ithstands LL=1800 V.
Insulated N-end (non-driven end) bearings and or
com ode filters are also required for motor
bearing currents with motors bigger than 100 kW.
Non-ABB 420 Insulation system must withstand LL=1300 V.
M otors 500 600 Standard insulation system conjunction with du/dt filtering reinforced insulation.2 ^s, du/dt filtering not
required.7. For information the construction of
Filter selection table for ACS800
the motor insulation, consult the manufacturer.
Symbol Explanation
U Nominal mains voltage.
500 600 the insulation system withstands LL=1800 u/dt filtering not required.
With du/dt filtering, the insulation system must withstand LL=1600 V