Basic Electrical Installation Work

| Kategorie: Kniha  |

Strana 368 z 399

Jak získat tento dokument?






Poznámky redaktora
5 Testing earth electrode resistance (612. Remove the test link and record the results schedule test results such as that given Appendix the IEE Regulations. Fix temporary link between the line and earth connections the consumer’s side the main switch. Remove all lamps and appliances. 14. 2. . Switch off the supply the main switch.7) Low-voltage supplies having earthing arrangements which are indepen- dent the supply cable are classified systems. For this type sup- ply necessary sink earth electrode into the general mass earth, which then forms part the earth return conjunction with RCD. the pin the right earth) and earth at each socket outlet shown Fig. Lights Switches Sockets Link L N Tester C C C FIGURE 14.e. 3. Test between the live pin (i. 6. For satisfactory test result the ohmmeter continuity meter should read very close zero for each test. 5. 4.Electrical installations and wiring systems 357 The test done with the supply disconnected using ohmmeter con- tinuity tester follows: 1. Test between the ‘common’ terminal and earth each switch position.71 Polarity test.71. Test between the centre pin any Edison screw lampholders and any convenient earth connection