Basic Electrical Installation Work

| Kategorie: Kniha  |

Strana 367 z 399

Jak získat tento dokument?






Poznámky redaktora
Remove all lamps. 3. these cases each circuit should separately tested obtain reading greater than 2MΩ. live and neutral conductors connected together) and the earthing arrangements may made. 2. Close all switches and circuit breakers. The insulation resistance readings for each test must not less than 1. To final circuits L N Tester (b) . 14. Record the results a schedule test results such that given Appendix the IEE Regulations. Remove all lamps.c.2). Although insulation resistance reading 1. The procedures are: Phase and neutral conductors earth 1.0MΩ (IEE Regulation 612.70 Insulation resistance test. Test separately between the line conductor and earth, and between the neutral conductor and earth, for every distribution circuit the consumer’s unit shown Fig. Disconnect appliances. 4. Disconnect appliances.70(b) and record the result. 4. 3.3.3. important make polarity test the installation since visual inspection will only indicate conduc- tor identification. Between line conductors 1. 14.6) The object this test verify that all fuses, circuit breakers and switches are connected the line live conductor only, and that all socket outlets are correctly wired and Edison screw-type lampholders have the centre contact connected the live conductor. To final circuits L N Tester (a) FIGURE 14.0MΩ for satisfactory result (IEE Regulation 612.70(a). 2.e.Basic Electrical Installation Work 356 should disconnected, since they will respectively glow, charge be damaged the test. The insulation resistance these tests should be not less than 1. There are two tests carried out using insulation resistance tester which must have test voltage 500 d. Where the circuit includes electronic equipment which might damaged by the insulation resistance test, measurement between all live conduc- tors (i. These are line and neutral conductors earth and between line conductors.0MΩ complies with the Regulations, the IEE Guidance Notes tell that much higher values than this can expected and that reading less than 2MΩ might indicate a latent but not yet visible fault the installation.3). Test between line and neutral conductors every distribution circuit at the consumer’s unit shown Fig. 4 Testing polarity (612. for 230 and 400 installa- tions. Close all switches and circuit breakers