2. Disconnect appliances. The insulation resistance these tests should be not less than 1. 14. for 230 and 400 installa- tions. 2.Basic Electrical Installation Work 356 should disconnected, since they will respectively glow, charge be damaged the test.70(b) and record the result. Remove all lamps. Remove all lamps. These are line and neutral conductors earth and between line conductors. To final circuits L N Tester (a) FIGURE 14.0MΩ complies with the Regulations, the IEE Guidance Notes tell that much higher values than this can expected and that reading less than 2MΩ might indicate a latent but not yet visible fault the installation. important make polarity test the installation since visual inspection will only indicate conduc- tor identification. 4. 4. Test between line and neutral conductors every distribution circuit at the consumer’s unit shown Fig. The procedures are: Phase and neutral conductors earth 1. 14. Close all switches and circuit breakers.6) The object this test verify that all fuses, circuit breakers and switches are connected the line live conductor only, and that all socket outlets are correctly wired and Edison screw-type lampholders have the centre contact connected the live conductor. To final circuits L N Tester (b) . these cases each circuit should separately tested obtain reading greater than 2MΩ.3. The insulation resistance readings for each test must not less than 1. 3.e. Although insulation resistance reading 1.0MΩ (IEE Regulation 612. Test separately between the line conductor and earth, and between the neutral conductor and earth, for every distribution circuit the consumer’s unit shown Fig. live and neutral conductors connected together) and the earthing arrangements may made. 4 Testing polarity (612. Close all switches and circuit breakers. Where the circuit includes electronic equipment which might damaged by the insulation resistance test, measurement between all live conduc- tors (i. Disconnect appliances.3). Between line conductors 1.70 Insulation resistance test.c.2).0MΩ for satisfactory result (IEE Regulation 612. There are two tests carried out using insulation resistance tester which must have test voltage 500 d. 3.3.70(a). Record the results a schedule test results such that given Appendix the IEE Regulations