Basic Electrical Installation Work

| Kategorie: Kniha  |

Strana 320 z 399

Jak získat tento dokument?






Poznámky redaktora
m m cable The sum the cable factors ) 43 10 43 203 ( From Table 14. Example 2 Ten 1.6: The factor for one cable The sum the cable fa 2 30 2 .5 times the outside diameter the conduit.6 Conduit Cable Factors.5 30 4 43 6 58 10 105 16 145 25 217 The inner radius conduit bend should not less than 2. . A 16mm conduit containing one bend only has factor 143 which less than 203, the sum of the cable factors and, therefore, 20mm conduit the minimum size contain these cables. Determine the minimum size conduit contain these conductors. From Table 14. Determine the minimum size conduit contain these cables. A 20mm conduit containing two bends only has factor 141 which less than 180, the sum of the cable factors and, therefore, 25mm conduit the minimum size contain these cables.5mm2 PVC insulated cables are run conduit containing two bends between boxes 10m apart.0mm2 PVC insulated cables are drawn into plastic conduit which long between boxes and contains one bend.5 22 2.7, 20mm conduit, long and containing one bend, has factor 233. .6: The factor for one cable The factor for one m 1 16 4 0 . 4. From Table 14. Adapted from the IEE Site Guide Kind Permission the Institution of Electrical Engineers Cable factors for use conduit long straight runs over 3m, or runs any length incorporating bends Type conductor Conductor cross- sectional area (mm2 ) Cable factor Solid stranded 16 1.7, 25mm conduit, 10m long and containing two bends, has factor 260.Electrical installations and wiring systems 309 Table 14. c ctors 6 30 180 From Table 14. Example 1 Six 2.0mm PVC insulated CPC also included