Selecting specific feature changes the structure the Parameter screen WinEDC. Features cannot enabled
through the E-LAN. used grids which damping resistors (NER) and residu-
al-current-increase resistors (Rw) are controlled and displayed.
In the following example, the command that entered the terminal screen italicized. The HPCI separate piece hardware (control cabinet). This feature can also enabled without pass-
word.
If this feature not enabled the factory, the following must entered the termi-
nal screen:
Please ask Eberle’s head office for the password.
This special feature. This function not necessary when the REG-DP/ REG-
DPA used its own.
– HPCI: High Power Current Injection.
This function charged separately and can enabled upon delivery later stage.
0 (current injection)
– Current injection This feature requires additional hardware (current injection cabi-
net).Page 93
Detailed description REG-DP/ REG-DPA parameters
When enabling feature, make sure that the regulator which the feature ena-
bled directly connected the through COM1 port. password protection
0 ENEL:
This function/feature only used with the EDC-Sys and not necessary when the REG-
DP/ REG-DPA used its own. password protection
0 CBR:
This special feature.
0 COM2FIX:
This parameter used fix the interface speed the REG-DP/ REG-DPA's COM2 port
.
0 PP_NO_COMM:
Setting this parameter enables system with several P-coils and regulators com-
municate without E-LAN.
0 EOR:
Is only used EDC-Sys devices