Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 57 z 272

Jak získat tento dokument?






Poznámky redaktora
All acknowledgeable errors are reset the same time.1 Non-resettable errors/critical errors are: 0 Status LED extinct the device must sent for inspection.4.6 Troubleshooting Figure 39: Troubleshooting (REG-DP error messages) Errors are displayed the status bar soon they occur.4. 0 Firmware error– the firmware doesn't match the used hardware 0 (current injection) not available 0 Blown fuse These messages display until the cause the error has been fixed. . If several error messages are displayed, use the keys scroll through them.Page 57 Operating the REG-DP directly Earthflt Number earth faults Time earth fault that longer than the set transient time Iw-Incr Number residual current increases When the additional resistor controlled the REG-DP Trigger Number search triggers The regulator goes into search mode; the regulator doesn't actually have to search for anything the original Uen value reached within the time delay SeachCI Number searches with optional current injection Note: This does not change the coil position externalCI Number external current injection requests; typical with EOR-DM (in EDCSys) for the admittance technique for earth fault detection 9. 9.6. Detailed information ob- tained pressing <MENU> <F5>. Press <F5> acknowledge error message