Page Operating the REG-DP directly
We take care it.
Measured value Description
I2_Phi Angle the current I2, relation Usync
Ipos Coil position A
Usync Absolute value the synchronization voltage.1 Displaying statistics
The statistics are displayed summary statistics statistics calendar weeks (CW).
<F3> used set the threshold that triggers new recording.
The zero sequence voltage Une stored logarithmically and displayed logarithmic
scale.
The following data are recoded statistics:
Parameters Description
Automatic Summary time Automatic mode: Overflow 100 000 h
Automatically switches the output days: d
Motor Summary time the adjustment commands 'Higher' and 'Lower'
The P-coil's 'Mot_Run' entry also taken into account.4.4 Statistics
9.
Standard allocation for the hidden channel: Angle Une
1 Caution:
When the value that set recorded recording channel changed, all the data
in the recorder are deleted. Press <F1> use the <> and <>
arrow keys scroll the different values displayed the below table.
9. the value changes more
than the resolution that set the recorder (in %), the new value used for the record-
ing.
Earth fault duration Summary time the earth faults including transient earth faults
Current injection Period during which the was active
Search Number started search processes
Tuned Number successful tuning processes
. This recording guarantees good resolution even for small zero sequence voltages
Standard allocation for the left channel: Ipos
<F2> Channel right graph (screen 2):
The options are the same for channel 1
Standard allocation for the right channel: Une
<F4> Channel (hidden) (screen 2):
Additional information can stored this channel, for example, the angle information of
the zero sequence voltage Une.4.4.
Press <F3> switch between the different screens