130 A). This curve also applies cable networks with to 20 nominal voltage with small component overhead cables even their neutral point isolated.Page 27 Applications If detuning specified percentage, the expected reactive current across the faulty section calculated according the following formula ( ) 100 res fix v I v I    (1. Ires equal the grid's capacitive current, when earth fault occurs Ifix Current connected fixed coil grid v Detuning % In very large grids, the values recommended VDE 0228 Part for the self-extinguishing current limit may exceeded (up kV: 110 ca.24) Iv Detuning current (reactive current A Ires Current through the adjustable P-coil the resonance point. Figure 11: Self-extinguishing current limit accordance with VDE 0228, Part 2 Curve Self-extinguishing current limit for earth-fault residual current for grids with earth-fault compensation. Curve Networks with isolated neutral point. nominal voltage earth fault curren t