Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 259 z 272

Jak získat tento dokument?






Poznámky redaktora
The battery not actively used long the device pow- ered auxiliary voltage. Please check the battery type the device. Battery replacement can also event-based. The battery serves backup the auxiliary voltage fails.6 DANGER! Danger electric shock! Injury death  When replacing the fuse, disconnect the device from all power supplies (auxiliary voltage, control voltages). The below delivery times are approximate. To replace the battery, first remove the plastic protective cover the CPU board. Once the battery has been changed, put the cover back on.3 Replacing the battery Three versions buffer battery are used the REG-DP Depending the version and year manufacture the device, the batteries are used for different purposes (see case descriptions this chapter). For more in- formation backing and restoring parameters, see Chapter 10. Regardless the type battery, the parameters should saved quickly possible in the event battery failure and always before the device disconnected from the supply voltage. This means that the battery does not have re- placed regular intervals. . Loosen the four screws and remove the cover. This doesn't have but can done devices equipped with MRAM.Page 259 Maintenance/Cleaning 17.2. In general, the battery voltage monitored and alarm set off (status relay sta- tus/operating LED) information (output function for weak battery) generated when the battery shows low residual capacity.3. result repairs, for example, old devices may need new CPU circuit board