Page 237 Commissioning the HPCI 0 algorithm Settings: Uns Ici: Default algorithm calculate the grid parameters Uns Uod If: Not possible for HPCI! Default setting: Uns Ici 0 cycl. Stimulate all If the zero sequence voltage the resonance curve extremely flat, relative change in the zero sequence voltage that caused switching operation will have very little im- pact the Une. It therefore meaningful stimulate the current injection calculate/check the grid pa- rameters regular intervals. Default setting: YES . Default setting: active 0 Emergency operation 'Move coil' If the communication the current injection controller fails, the REG-DP/ REG-DPA can switch classic regulation moving the coil. NO: The REG-DP/ REG-DPA not allowed move the coil determine the resonance curve current not injected The regulator goes into alarm state. Example every min Default setting: min inactive) 0 New search after positioning If the checkbox for this parameter checked, the REG-DP/ REG-DPA will perform control measurement after successful tuning check the resonance curve again. Settings: YES: The REG-DP/ REG-DPA allowed move the coil determine the res- onance curve current not injected. the value the same, the coil will stay this position. stays alarm state for more than 60s, the regulator will go into error state and switch MAN