Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 237 z 272

Jak získat tento dokument?






Poznámky redaktora
It therefore meaningful stimulate the current injection calculate/check the grid pa- rameters regular intervals. Default setting: active 0 Emergency operation 'Move coil' If the communication the current injection controller fails, the REG-DP/ REG-DPA can switch classic regulation moving the coil. NO: The REG-DP/ REG-DPA not allowed move the coil determine the resonance curve current not injected The regulator goes into alarm state. Settings: YES: The REG-DP/ REG-DPA allowed move the coil determine the res- onance curve current not injected. Example every min Default setting: min inactive) 0 New search after positioning If the checkbox for this parameter checked, the REG-DP/ REG-DPA will perform control measurement after successful tuning check the resonance curve again.Page 237 Commissioning the HPCI 0 algorithm Settings: Uns Ici: Default algorithm calculate the grid parameters Uns Uod If: Not possible for HPCI! Default setting: Uns Ici 0 cycl. the value the same, the coil will stay this position. stays alarm state for more than 60s, the regulator will go into error state and switch MAN. Default setting: YES . Stimulate all If the zero sequence voltage the resonance curve extremely flat, relative change in the zero sequence voltage that caused switching operation will have very little im- pact the Une