2 Enabling HPCI the WinEDC terminal
Alternatively, the HPCI feature can directly enabled WinEDC
by entering the command: feature 2
Press ENTER confirm.1.6 Testing communication between the HPCI module and REG-
DP/ REG-DPA
To use current injection, the HPCI feature must enabled.
The following error message displayed:
Message: Current injection not available
If the communication the current injection controller available, the error message will
disappear.
Figure 165: Enabling the HPCI feature WinEDC's Terminal screen
14.Page 235
Commissioning the HPCI
14.
The correct connection between the regulator (COM3) and the CIC's COM3 (current injec-
tion controller) follows:
REG-DP/
REG-DPA
CIC
.
The error indicated directly the regulator the illumination the error LED and on
the 'Troubleshooting' screen.5.
If the COM3 connection between REG-DP/ REG-DPA does not exist faulty, error will
display the regulator soon the HPCI feature enabled. This described Chapter 1