Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 222 z 272

Jak získat tento dokument?






Poznámky redaktora
Connection Notes Supply voltage (400 V/230 AC, L1, L2, N) Fused internally with (internally over Q2) CAUTION: not use circuit breaker! Use isolating transformer 2.2.5 kVA) instead Use 2.  The right choice measurement points such zero sequence voltage and the measure- ment the current injected when HPCI used the same for classic current injection and described Chapter13. Only five connections are needed install/retrofit HPCI.2. Based the pulse pattern, 100 can flow when an earth fault occurs. Separate voltage transformer the coil External voltage transformer Measurement open delta winding the busbar PAW On the power auxiliary winding Use connection cable that least mm 2 COM3 connection REG-DP/ REG- DPA 4-wire RS-485 connection Use shielded and twisted 2x2 core cable Small signal line! .2 Connections HPCI Connection the power auxiliary winding must least mm2 !  The connection the P-coil's power auxiliary winding has separate fuse for each in- ductor. fuses are used.Page 222 Commissioning the HPCI We take care it.5 mm 2 cable Supply voltage (230 L1-N) Fused internally with (internally over Q1) CAUTION: fuse can used! UNE Measurement zero sequence voltage Ideal voltage transformer that not measuring the same magnetic circuit the power auxiliary winding. 14