0 Current injection now continuous and new resonance curves are constantly calculat-
ed.
13.10 Completing the commissioning current injection
After successful polarity test, the regulator can set AUTO mode and the resonance
curve calculated.
.
During the adjustment, the calculated value for Ires and should good constant.
0 Enter 100% for the power and press the 'Accept' key.
The calculated resonance curve and the value for Ires are displayed the REG-DP/ REG-
DPA.
Note:
If the regulation parameter still set 'Move coil', set back 'Current injection'.
0 Move the coil manually (using the Higher and Lower keys the device) from the upper
to the lower end switch.
13.11 Verifying the correct calculation across the P-coil's whole
adjustment range
0 The REG_DP(A) must set MAN!
0 Select manual current injection the WinEDC service screen.Page 212 Commissioning current injection