Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 199 z 272

Jak získat tento dokument?






Poznámky redaktora
Enter the command: feature 1 Press ENTER confirm.Page 199 Commissioning current injection 13. The error indicated directly the regulator the illumination the error LED and on the 'Troubleshooting' screen.6. . Figure 135: Enabling the feature WinEDC's Terminal program 13. If the COM3 connection the REG-DP/ REG-DPA does not exist faulty, error will display the regulator soon the feature enabled. This described Chapter 13.2 Enabling the WinEDC terminal Alternatively, the feature can enabled WinEDC.6. The following error message displays: Current injection not available If the communication the current injection controller available, the error message will disappear.7 Testing communication between current injection and the REG-DP/ REG-DPA To use current injection, the feature must enabled