Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 199 z 272

Jak získat tento dokument?






Poznámky redaktora
Page 199 Commissioning current injection 13.6.7 Testing communication between current injection and the REG-DP/ REG-DPA To use current injection, the feature must enabled.2 Enabling the WinEDC terminal Alternatively, the feature can enabled WinEDC. Enter the command: feature 1 Press ENTER confirm.6. The error indicated directly the regulator the illumination the error LED and on the 'Troubleshooting' screen. Figure 135: Enabling the feature WinEDC's Terminal program 13. This described Chapter 13. If the COM3 connection the REG-DP/ REG-DPA does not exist faulty, error will display the regulator soon the feature enabled. . The following error message displays: Current injection not available If the communication the current injection controller available, the error message will disappear