Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 161 z 272

Jak získat tento dokument?






Poznámky redaktora
5. 11.5.Page 161 Detailed description REG-DP/ REG-DPA parameters 11.1.2 Options 0 Reset behaviour The state which the regulator should switch after auxiliary voltage loss the regula- tor set here. Figure 107: Symbol the display for continuous operation ==> Continuous operation indicated the second line the REG-DP/ REG-DPA's display by this symbol >.3 Display 0 Display Une in Settings: Value Description % Uen the nominal value (100 V) V Uen secondary value the voltage transformer V kV Uen primary value the voltage transformer. Settings: Value Description Unchanged the REG-DP/ REG-DPA was previously AUTO mode, will resume regula- tion soon the supply voltage has been restored MAN The REG-DP/ REG-DPA switches into MAN mode after the supply voltage has been restored 0 Higher/Lower continuous operation If this value set active, long press seconds) the Higher Lower key will set the position command for the coil Locking. The Higher Lower command will output un- til the Higher Lower key pressed again.1