0 Use fix coil value
Settings:
Requires the P-coil measure the current.
Settings:
Setting Description
OFF: The fix coil not controlled the REG-DP/ REG-DPA
ON The fix coil always through the REG-DP/ REG-DPA
<AUTO> The REG-DP/ REG-DPA can automatically switch the fix coil off when
the adjustment range for the automatic coil not sufficient
Additional values for the fix coil that are only visible when current injection (CI feature) is
used:
0 Quality the fix coil
The quality the fix coil is:
( )
( )
fix
fix
imag I
Q
real I
Only calculated when current injection used with available fix coil information. This function only makes sense when the ENEL
feature used together with EDC-Sys.3 SCADA system
Figure 105: Menu item SCADA system
This where the network parameters are set for the connected protocol card (REG-PE or
REG-PED).
.
0 Measured fix coil
See comments 'Use fix coil' cannot changed
0 Measured quality
See comments 'Use fix coil' cannot changed
11.Page 159
Detailed description REG-DP/ REG-DPA parameters
0 Fixed coil control
The regulator can control the fix coil (if desired) when the adjustment range the coil that
is regulated REG-DP/ REG-DPA not sufficient.4