Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 144 z 272

Jak získat tento dokument?






Poznámky redaktora
 Remove jumper for the normally closed function, leave jumper for normally open func- tion. Note: An error not generated the slide-in device pulled out.Page 144 Detailed description REG-DP/ REG-DPA parameters We take care it.1. Status relay with normally open function: The contact closes when error occurs. The status relay's normally open contact is selected through the jumper.4 The status relay (normally open contact normally closed contact) Note (Order Codes): By using the right jumper configuration, the binary output 'Status' can used either a 'normally closed' 'normally open' contact. The status relay's normally closed contact is selected through the jumper. The position the jumper displayed Fig- ure 95). The relay coil not excited when error occurs. The status relay energized the regulator's healthy state. Note: The following errors are also sent the SCADA system 0 Pulled out slide-in device 0 Auxiliary voltage failure the regulator 0 Regulator for internal errors  Remove jumper for normally open contact function, leave jumper for normally closed contact.4. Jumpers are used determine whether the contact open closed when error occurs. 11. REG-REL-3 Status Relay “Break“ function “Make“ function Figure 94: Position the jumper PCB. The relay coil not excited when error occurs. Status relay with normally closed function: The contact opens when error occurs. The function (jumper) that not used must removed