Note:
The following errors are also sent the SCADA system
0 Pulled out slide-in device
0 Auxiliary voltage failure the regulator
0 Regulator for internal errors
Remove jumper for normally open contact function, leave jumper for normally closed
contact.
Remove jumper for the normally closed function, leave jumper for normally open func-
tion.
Status relay with normally open function: The contact closes when error occurs.
11. The status relay's normally closed contact
is selected through the jumper.4.4 The status relay (normally open contact normally closed contact)
Note (Order Codes):
By using the right jumper configuration, the binary output 'Status' can used either a
'normally closed' 'normally open' contact. Jumpers are used determine
whether the contact open closed when error occurs.
The status relay energized the regulator's healthy state.
Note:
An error not generated the slide-in device pulled out.
The relay coil not excited when error occurs. The status relay's normally open contact
is selected through the jumper.1.Page 144 Detailed description REG-DP/ REG-DPA parameters
We take care it. The function (jumper) that not used must removed. The position the jumper displayed Fig-
ure 95).
Status relay with normally closed function: The contact opens when error occurs.
The relay coil not excited when error occurs.
REG-REL-3
Status Relay
“Break“ function “Make“ function
Figure 94: Position the jumper PCB