Remove jumper for the normally closed function, leave jumper for normally open func-
tion.4.
The relay coil not excited when error occurs.
The status relay energized the regulator's healthy state.
Status relay with normally open function: The contact closes when error occurs. The function (jumper) that not used must removed.1.
The relay coil not excited when error occurs. The status relay's normally closed contact
is selected through the jumper.
Note:
An error not generated the slide-in device pulled out. The status relay's normally open contact
is selected through the jumper.
REG-REL-3
Status Relay
“Break“ function “Make“ function
Figure 94: Position the jumper PCB. The position the jumper displayed Fig-
ure 95).
11.4 The status relay (normally open contact normally closed contact)
Note (Order Codes):
By using the right jumper configuration, the binary output 'Status' can used either a
'normally closed' 'normally open' contact.Page 144 Detailed description REG-DP/ REG-DPA parameters
We take care it. Jumpers are used determine
whether the contact open closed when error occurs.
Status relay with normally closed function: The contact opens when error occurs.
Note:
The following errors are also sent the SCADA system
0 Pulled out slide-in device
0 Auxiliary voltage failure the regulator
0 Regulator for internal errors
Remove jumper for normally open contact function, leave jumper for normally closed
contact