The status relay's normally closed contact
is selected through the jumper.
Note:
An error not generated the slide-in device pulled out.1.4 The status relay (normally open contact normally closed contact)
Note (Order Codes):
By using the right jumper configuration, the binary output 'Status' can used either a
'normally closed' 'normally open' contact.
The status relay energized the regulator's healthy state.
Status relay with normally open function: The contact closes when error occurs. The status relay's normally open contact
is selected through the jumper.
Status relay with normally closed function: The contact opens when error occurs. The position the jumper displayed Fig-
ure 95).
The relay coil not excited when error occurs.
11.
The relay coil not excited when error occurs.
Note:
The following errors are also sent the SCADA system
0 Pulled out slide-in device
0 Auxiliary voltage failure the regulator
0 Regulator for internal errors
Remove jumper for normally open contact function, leave jumper for normally closed
contact. The function (jumper) that not used must removed.Page 144 Detailed description REG-DP/ REG-DPA parameters
We take care it.
REG-REL-3
Status Relay
“Break“ function “Make“ function
Figure 94: Position the jumper PCB.
Remove jumper for the normally closed function, leave jumper for normally open func-
tion.4. Jumpers are used determine
whether the contact open closed when error occurs