Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 144 z 272

Jak získat tento dokument?






Poznámky redaktora
4. Note: An error not generated the slide-in device pulled out. The status relay energized the regulator's healthy state. Status relay with normally open function: The contact closes when error occurs. The position the jumper displayed Fig- ure 95). Note: The following errors are also sent the SCADA system 0 Pulled out slide-in device 0 Auxiliary voltage failure the regulator 0 Regulator for internal errors  Remove jumper for normally open contact function, leave jumper for normally closed contact. The function (jumper) that not used must removed.1. Jumpers are used determine whether the contact open closed when error occurs. The status relay's normally closed contact is selected through the jumper. REG-REL-3 Status Relay “Break“ function “Make“ function Figure 94: Position the jumper PCB.4 The status relay (normally open contact normally closed contact) Note (Order Codes): By using the right jumper configuration, the binary output 'Status' can used either a 'normally closed' 'normally open' contact. The status relay's normally open contact is selected through the jumper. 11. The relay coil not excited when error occurs.Page 144 Detailed description REG-DP/ REG-DPA parameters We take care it. The relay coil not excited when error occurs. Status relay with normally closed function: The contact opens when error occurs.  Remove jumper for the normally closed function, leave jumper for normally open func- tion