Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 128 z 272

Jak získat tento dokument?






Poznámky redaktora
Notes: 0 This procedure not restricted two regulators. 11. 0 With this procedure, also not possible determine whether each regulator will take over a specific part the compensation. 0 This procedure should not used the strategy consists breaking down the main grid into many smaller grids when earth fault occurs.4. The time adjust the whole grid increases with the number regulators that are switched parallel.4. The compensation condition only met for the whole grid.1 Measurement Figure 90: Menu: REG-DP Measurement .1. The actual zero sequence voltage and the set trigger threshold are used reference value for the tolerance band. regulators have finished their tuning processes.1 Parallel regulation without communication with current injection Current injection can significantly accelerate the above-described time-consuming behav- iour.3.4. 0 Regulator REG-DP/ REG-DPA 0 Coil 11.Page 128 Detailed description REG-DP/ REG-DPA parameters We take care it.4 Menu item Commissioning This menu item can broken down into two blocks. The precondition regulation with current injection and activated parallel regulation with- out communication. 11.1 REG-DP/ REG-DPA 11