Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 112 z 272

Jak získat tento dokument?






Poznámky redaktora
Moreover, high zero sequence voltage healthy grid in- creased continuous load for the insulation single phase. Note: The parameters Umax_End_Threshold, Umax_End_Priority and Umax_Hysteresis apply tuning performed AUTO mode. 0 100 10 -2 10 -1 10 0 10 1 Coil position [%] Une in [%] Self-extinguishing current limit detuning Umax_end_threshold Umax_end hysteresis Figure 81: Umax_End and self-extinguishing current limit; Description 0 Umax_End threshold This value used set maximum zero sequence voltage for the tuning point. A value disables the 'Umax_End' function. Default setting: s Note: The parameters Umax_Threshold, Umax_Delay and Umax_Hysteresis apply search pro- cesses performed AUTO mode. Default setting:.Page 112 Detailed description REG-DP/ REG-DPA parameters We take care it. If, for ex- ample, the zero sequence voltage too high the target tuning point, the coil moved away from the resonance point until the smaller zero sequence voltage Umax_End has been reached. The regulator displays 'Tune'. this case, the line-to-earth- voltage must added the zero sequence voltage (absolute value and phase). This function makes sense very unbalanced grids with big zero sequence voltage the resonance point. This why it possible have too high voltage for least one line-to-earth-voltage. Too high zero sequence voltage the tuned state can overexcite earth fault detection systems