The states the binary inputs must allocat-
ed the switch information the feeders. The coil adjusted
to the resonance point and the current correction.
If, the other hand, switch-offs switches other grids are performed isolate the
earth fault, the current coil position must corrected the absolute value the switch-
off switch.
At the end the transient earth fault time, the P-coil
is adjusted the last calculated resonance point. The determination the
correction value described further down.
Correction table when the CORR_TAB feature is
selected.Page 108 Detailed description REG-DP/ REG-DPA parameters
We take care it.
b)
Ires+Correction Combination Ires and correction. this case, the P-coil is
adjusted the last calculated resonance point.
c)
The correction table displayed when the CORR_TAB feature selected the 'General'
menu.
If lines are not switched off detect faults, 'Ires' can selected.
Parameters Description Examples in
Figure 77:
None The coil position not readjusted when earth fault
occurs.
a)
Tuning+Correction Readjust set value
At the end the transient earth fault time, the P-coil
is readjusted set value.
The values dIc_1 dIc_4 enable the coil posi-
tion corrected for lines when earth
fault occurs.
The value for the corresponding binary input
could be, for example, Ear_Corr1 for the feeder
for dIc_1.
.
Ires Readjust the resonance point