Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 108 z 272

Jak získat tento dokument?






Poznámky redaktora
this case, the P-coil is adjusted the last calculated resonance point. The value for the corresponding binary input could be, for example, Ear_Corr1 for the feeder for dIc_1. b) Ires+Correction Combination Ires and correction. The states the binary inputs must allocat- ed the switch information the feeders. If lines are not switched off detect faults, 'Ires' can selected. The coil adjusted to the resonance point and the current correction.Page 108 Detailed description REG-DP/ REG-DPA parameters We take care it. Parameters Description Examples in Figure 77: None The coil position not readjusted when earth fault occurs. Ires Readjust the resonance point. If, the other hand, switch-offs switches other grids are performed isolate the earth fault, the current coil position must corrected the absolute value the switch- off switch. Correction table when the CORR_TAB feature is selected. a) Tuning+Correction Readjust set value At the end the transient earth fault time, the P-coil is readjusted set value. The determination the correction value described further down. The values dIc_1 dIc_4 enable the coil posi- tion corrected for lines when earth fault occurs. At the end the transient earth fault time, the P-coil is adjusted the last calculated resonance point. . c) The correction table displayed when the CORR_TAB feature selected the 'General' menu