This Notification of Test Results is the result of testing a sample of the product subrrft ed, in acc rdancewith the provisions of the relevant specific standard.
............. 0,42 mm, 2,7 mm
P
During the test: terminals show damage
P
10..:
4 mm2 P
Afterthe test, terminál not damaged P
10.........................105 Secureness test:
during the test: the conductor does not slip out, no
break near clamping unit and damage
See appended table 10................104...................... mm2 P
Type................................:
0,14 mm2”f P
Connection/disconnection times: largest diameter
(mm)..106 Pull test:
- during the test the conductor does not come out See appended table 10..103 Terminals accept rigid and flexible conductors
(table 101), unless otherwise specified (see 8.....1 Connecting devices allow correct connection of
conductors P
10......................105
P
10.1)
P
Smallest diameter (mm); largest diameter (mm)................2 Rated cross-sectional area (mm2) .....................: rigid and flexible P
After the test, wire conductor escaped outside
the terminál
P
10................1 Conneetion/disconnection times: smallest diameter
(mm)................104 Terminals clamp the conductor without undue damage:
10.............101 Connection disconnection: use generál tool or
simple insertion
lever operated
P
Disconnection operation other than pull lever operated
P
10........................106...... 0,14 mm2”f”
0,2 mm2- mm2
P
Suitable for connecting cross-sectional areas (mm2) 0,14 mm2”f ’
0,2 mm2- mm2
P
10....102 Temninals accept two more conductors same different nominal cross-
sectional areas; see table 101 (as specified manufacturer):
P
Universal terminals shall accept rigid(solid stranded) and flexible unprepared
conductors
P
Non-universal terminals shall accept the types conductors declared the
manufacturer
P
Rated connecting capacity (mm2) ........104..........DEKRA
IEC 60998-2-2
Clause Requirement Test Result Remark Verdíct
10 CONNECTION CONDUCTORS
10.