Certifikáty krabicové svorky WAGO 221

| Kategorie: Certifikáty  | Tento dokument chci!

This Notification of Test Results is the result of testing a sample of the product subrrft ed, in acc rdancewith the provisions of the relevant specific standard.

Vydal: WAGO Elektro spol. s r.o. Autor: DEKRA

Strana 20 z 26

Jak získat tento dokument?






Poznámky redaktora
................IEC 60998-2-2 Clause Requirement Test Result Remark Verdict 15............ mm2rigid flexible Test current (Table (A)................................................. A Measured voltage drop of: Measured voltage drop (mV) Sample Sample Sample 3 Solid conductors (after cycles) 2,31 2,10 2,00 P Stranded conductors (after cycles) 2,12 2,23 2,10 P Flexible conductors (after cycles) 2,00 2,50 2,64 P Solid conductors (1,5 times 24mcycle value) 3,46 3,15 3,00 P Stranded conductors (1,5 times 24thcycle value) 3,18 3,34 3,15 P Flexible conductors (1,5 times 24lhcycle value) 3,00 3,75 3,96 P Solid conductors (after 192 cycles) 1,85 1,83 1,87 P Stranded conductors (after 192 cycles) 1,79 1,81 1,80 P Flexible conductors (after 192 cycles) 2,00 2,50 2,64 P Supplementary information: .......... 0,14 mm2flexible Test current (Table (A)..........101 TABLE: Temperature-cycling test Model/type reference.........: 2A Measured voltage drop of: Measured voltage drop (mV) Sample Sample Sample 3 Solid conductors (after cycles) Stranded conductors (after cycles) Flexible conductors (after cycles) 1,31 1,40 1,36 P Solid conductors (1,5 times 24,hcycle value) Stranded conductors (1,5 times 24thcycle value) Flexible conductors (1,5 times 24thcycle value) 1,96 2,10 2,04 P Solid conductors (after 192 cycles) Stranded conductors (after 192 cycles) Flexible conductors (after 192 cycles) 0,89 1,01 0,99 P Largest cross-sectional area (mm2)........: 221-415 Smallest cross-sectional area (mm2) .................................................