This Notification of Test Results is the result of testing a sample of the product subrrft ed, in acc rdancewith the provisions of the relevant specific standard.

Vydal: WAGO Elektro spol. s r.o. Autor: DEKRA

Strana 17 z 26

Jak získat tento dokument?






Poznámky redaktora
..... 0,45 0,44 0,44 P - voltage drop measured (mV) (3rddeflection).. 0,46 0,46 0,45 P - voltage drop measured (mV) (11”1deflection).............................................................: 0,46 0,45 0,45 P - requirement: 2,5....IEC 60998-2-2 Clause Requirement Test Result Remark Verdict 14...................... 0,4 P smallest cross-sectional area (mm2) 10........ 0,09 P Distance (mm) (table 104).101 TABLE: Mechanical strength 0,1 times the test current (A).............103 . 0,45 0,45 0,45 P - voltage drop measured (mV) (5lhdeflection)............ 0,46 0,45 0,45 P - voltage drop measured (mV) (4thdeflection)..... 0,46 0,44 0,45 P - voltage drop measured (mV) (6thdeflection). 100 P -screwless terminál number - - voltage drop measured (mV) (1stdeflection).. 0,2 mm2 P force (N) (table 104) . 0,46 0,45 0,45 P - voltage drop measured (mV) (7mdeflection)... 0,45 0,45 0,45 P - voltage drop measured (mV) (10thdeflection)................ 0,45 0,45 0,45 P - voltage drop measured (mV) (12thdeflection).... 0,42 0,43 0,43 P - voltage drop measured (mV) (2nddeflection)..... 0,45 0,45 0,44 P - voltage drop measured (mV) (8thdeflection)....... 0,46 0,46 0,45 P - voltage drop measured (mV) (9thdeflection)...............