This Notification of Test Results is the result of testing a sample of the product subrrft ed, in acc rdancewith the provisions of the relevant specific standard.

Vydal: WAGO Elektro spol. s r.o. Autor: DEKRA

Strana 17 z 26

Jak získat tento dokument?






Poznámky redaktora
........................... 0,2 mm2 P force (N) (table 104) ....... 0,46 0,46 0,45 P - voltage drop measured (mV) (9thdeflection)................ 0,45 0,45 0,45 P - voltage drop measured (mV) (10thdeflection).........: 0,46 0,45 0,45 P - requirement: 2,5.....101 TABLE: Mechanical strength 0,1 times the test current (A).IEC 60998-2-2 Clause Requirement Test Result Remark Verdict 14.............................. 0,46 0,44 0,45 P - voltage drop measured (mV) (6thdeflection)............... 0,42 0,43 0,43 P - voltage drop measured (mV) (2nddeflection)............. 0,4 P smallest cross-sectional area (mm2) 10... 0,45 0,45 0,45 P - voltage drop measured (mV) (12thdeflection).. 0,09 P Distance (mm) (table 104).. 0,45 0,45 0,45 P - voltage drop measured (mV) (5lhdeflection)............ 0,45 0,45 0,44 P - voltage drop measured (mV) (8thdeflection).......... 0,46 0,46 0,45 P - voltage drop measured (mV) (11”1deflection). 0,45 0,44 0,44 P - voltage drop measured (mV) (3rddeflection)................. 0,46 0,45 0,45 P - voltage drop measured (mV) (7mdeflection).... 0,46 0,45 0,45 P - voltage drop measured (mV) (4thdeflection)......... 100 P -screwless terminál number - - voltage drop measured (mV) (1stdeflection)...103 ..