Poznámky redaktora
-
- Five device configurations can selected.
Dimming channels
-
- Four individually-controllable dimming channels. mm²
Dimensions
-
- Modular widths (MW): 4
Notes
-
- Electronic ballasts generate very high current spikes.
-
- Block function forced setting function can parameterised.
-
- Reactions case bus voltage failure and restoration can be
set following ETS programming process.
-
- Time functions (switch-on, switch-off delay, staircase light
function also with advance warning function).
-
- Manual actution outputs independent the bus with
mechanical switching position indication.
-
- Group feedback all switching conditions possible.
-
- Feedback switching condition and brightness value.
-
- Logical linking function configurable per channel.
Scope supply
-
- KNX connection and junction terminal included the scope of
supply.
DRA plus 218000 2180 66
Features
-
- The DALI gateway Plus forms the interface between KNX
installation and digital DALI lighting system. four dimming channels are assigned
to one switching relay control RGBW light).
-
- Relay outputs that are not associated with dimming channel
can used freely-acting switching actuator channel.
-
- contact contact operation.
-
- Soft switch-on and soft switch-off function
-
- Block function forced setting function can parameterised. unit Specifications Order No.
-
- Dimmable brightness range can set.
-
- Dimming behaviour and dimming characteristics can be
parameterised.
-
- light scenes. This leads the
assignment four individually-controllable dimming channels to
the switching outputs (e.
-
- Time functions (switch-on delay, switch-off delay, staircase light
function). 100 mA
-
- Cable length: max.
-
- Effect control can configured for max.
-
- Cyclical monitoring incoming switching telegram is
configurable.
-
- Manual actuation the devices also independent the bus (also
building site operation with broadcast control). ten internal scenes
per switching output are programmable.526
KNX Dimming
Specifications Order No. sequences to
500 run-throughs (or infinite).
Technical data
KNX medium: TP1-256
Relay
-
- Number: 4
-
- Contact: zero-voltage contact
each, flip-flop
Control outputs
-
- Control voltage: V
-
- Control current per output: max. With the staircase light function, the reaction the
end the switch-on time can configured. groups, central control via a
broadcast telegram (group each with max.
-
- Switch-on times the relay outputs can recorded and
evaluated the elapsedoperating time meter.
-
- The groups can integrated the light scenes.
-
- Control max.
-
- Inclusion dimming channel ten scenes possible. operating
devices). unit PS
Gira electrical installation systems Price system (PS) 14: reduced discount
KNX
system
devices,
actuators,
sensors
DRA plus 222400 2224 26
Features
-
- The controller unit switches and dims electrical devices that have
a 1-10 interface.5 mm²
Switching outputs
-
- Switching voltage: 250/400 V
-
- Switching current 230 AC1: A
-
- Switching current 230 AC3: A
-
- Switching current 400 AC1: A
-
- Switching current 400 AC3: A
-
- Fluorescent lamps: AX
Lamp loads
-
- Light bulbs: 3680 W
-
- halogen lamps: 3680 W
-
- Wound transformer: 2000 VA
-
- Gira Tronic transformer: 2500 W
Fluorescent lamps T5/T8
-
- Uncompensated: 3680 W
-
- Parallel-compensated: 2500 W/200 µF
-
- Duo-circuit: 3680 W/200 µF
Compact fluorescent lamps
-
- Uncompensated: 3680 W
-
- Parallel-compensated: 2500 W/200 µF
Mercury-vapour lamps
-
- Uncompensated: 3680 W
-
- Parallel-compensated: 3680 W/200 µF
Ambient temperature: +45 °C
Connections
-
- KNX: Connection and junction terminal
-
- Screw terminals
-
- Load: Screw terminals
-
- max.
KNX control unit 4-gang with manual
actuation
KNX DALI gateway Plus
.g.
-
- Can integrated the light scenes.
-
- The burning-in function allows for the start-up new fluorescent
lamps prescribed lighting manufacturers.
Switching actuator operation (optional)
-
- Independent switching switch outputs A4.
-
- Feedback from the switching condition. For this
reason, use switch-on current limiter separate load contact
for with greater loads.
-
- Active passive (object can read out) cyclical feedback
function.
-
- Energy-saving function: Switch-off the power supply the
DALI operating devices possible switched-off state (via
additional KNX switching actuator). DALI operating devices individual control,
group control max.
-
- Feedback DALI error status short circuit and signalling of
power supply failure.
-
- three central switching functions for the joint control all
dimming and switching channels. 500 0.
-
- Delay for actively transmitted feedback messages following bus
voltage recovery