Poznámky redaktora
-
- Group feedback for reduction bus load.
-
- Logical linking function for each output.
-
- Central switching function.
-
- Time functions (switch-on/off delay, staircase light function –
also with advance warning function).
Blind functions
-
- Separately parameterisable movement times with movement time
extension for moving into the upper end position. mm²
Dimensions
-
- Modular widths (MW): 4
Scope supply
-
- KNX connection and junction terminal included the scope of
supply. an
alternative, forced setting function for each output. Mixed configurations of
switching and blind actuators are also possible.
Technical data
Relay
-
- Number: 4
-
- Contact: zero-voltage contact each
Current capacity
-
- neighbouring outputs: Total A
-
- Device: Total A
Connections: max.
-
- Independent switching eight switching outputs.
Technical data
Relay
-
- Number: 8
-
- Contact: zero-voltage contact each
Current capacity
-
- neighbouring outputs: Total A
-
- Device: Total A
Connections: max.
-
- Feedback the curtain position slat position.
-
- Different external conductors may connected the outputs.
Technical data
KNX medium: TP1-256
Power supply: 230 50/60 Hz
Switching capacity 230 AC1
Maximum switch-on current: 800 200 µs, 165 ms
Connected load
-
- Ohmic load: 3000 W
-
- Capacitive load 230 max. unit Specifications Order No.
-
- Central control all blind outputs possible. 140 µF
-
- Motors (blind fan): 1380 W
-
- Light bulbs: 3000 W
-
- halogen lamps: 2500 W
-
- Wound transformer: 1200 VA
-
- Gira Tronic transformer: 1500 W
-
- Fluorescent lamps,
uncompensated:
1000 VA
-
- Fluorescent lamps, duo-
circuit:
2300 VA
-
- Fluorescent lamps, parallel-
compensated:
1160 VA
-
- Mercury-vapour lamps,
uncompensated:
1000 W
-
- Mercury-vapour lamps,
parallel-compensated:
1160 W
Connections
-
- KNX: Connection and junction terminal
-
- Load: Screw terminals
Notes
-
- Installation DIN top-hat rail.
Features
-
- Switching status indication for each relay.
-
- With integrated bus coupler.
-
- Manual actuation for changing over the relays parallel or
without KNX operation.
-
- Behaviour after bus voltage failure and recovery can set.
-
- Feedback can delayed until after the recovery bus voltage.
-
- Active passive (object can read out) cyclical feedback
function.
-
- Memory function for light scenes.
Switching blinds KNX switching actuator, 4-gang blind
actuator, 2-gang with manual actuation
KNX switching actuator, 8-gang blind
actuator, 4-gang with manual actuation
.
-
- Independent switching four switching outputs.
-
- Integration scenes possible, internal scenes the most
can parameterised per channel. For the blind
actuator function, two neighbouring relay outputs are combined to
form one blind output. unit PS
Price system (PS) 14: reduced discount Gira electrical installation systems
KNX
system
devices,
actuators,
sensors
Depending the parameterisation, the actuator can used a
switching actuator blind actuator.
-
- Block function can parameterised for each channel.
-
- Sun protection function with fixed and variable curtain slat
positions can activated.
-
- Assignments five different safety functions (three wind
alarms, one rain alarm, one frost alarm) optionally with cyclical
monitoring.
-
- Building site operation: Outputs can operated manually
without bus voltage with operating voltage only.
-
- Central switch-off possible per manual actuation.
Scope supply
-
- KNX connection and junction terminal included the scope of
supply.
-
- Forced setting function can realised for each blind output.519
Switching blinds KNX
Specifications Order No.
DRA plus 103600
1036 1/100 66
Features
-
- Independent control two blind outputs.
Switching functions
-
- contact contact operation can set.
DRA plus 103700
1037 1/100 66
Features
-
- Independent control four blind outputs.
-
- Behaviour after bus voltage failure and recovery can set. mm²
Dimensions
-
- Modular widths (MW): 4
Notes
-
- VDE approval accordance with 60669-1, 60669-2-1