Poznámky redaktora
Technical data
KNX medium: TP1-256
Connections
-
- KNX: Connection and junction terminal
-
- Load: Screw terminals
Notes
-
- Installation DIN top-hat rail.
-
- Reactions case bus voltage failure and restoration can be
set for each channel following ETS programming process.
-
- Active passive (object can read out) cyclical feedback
function.
-
- Group feedback for reduction bus load.
-
- contact contact operation.
-
- Block function can parameterised for each channel.
-
- Time functions (switch-on/off delay, staircase light function –
also with advance warning function).516
KNX Switching
Specifications Order No.
-
- Integration light scenes possible, eight internal scenes the
most can parameterised per channel. an
alternative, forced setting function for each output. For switching
independently controllable groups loads.
-
- Feedback can delayed until after the recovery bus voltage. additional power supply required.
-
- Central switching function. unit PS
Gira electrical installation systems Price system (PS) 14: reduced discount
KNX
system
devices,
actuators,
sensors
DRA switching actuators with integrated bus coupler.
DRA plus 104000
1040 1/100 26
Features
-
- Independent switching the two outputs.
Features
-
- Manual actuation the relay independent the bus or
switching position indication.
-
- VDE approval accordance with 60669-1, 60669-2-1. unit Specifications Order No.
Multi-phase connection.
-
- Elapsed operating time meter forward/backward counter with
limit function (limit can changed via bus) can activated for
each output.
Switching KNX switching actuator, 2-gang with manual
actuation
.
-
- Input monitoring for cyclical updating with safety setting.
Technical data
Relay
-
- Number: 2
-
- Contact: zero-voltage contact
each, flip-flop
Switching capacity
-
- 230 AC1 AC3
-
- 400 AC1 AC3
-
- DC: A/24 V
Maximum switch-on current: 400 150 µs, 200 600 µs
Connected load
-
- Ohmic load: 3600 W
-
- Capacitive load 230 max. With manual switch for
switching over the relay (On/Off) parallel without KNX operation. mm²
Dimensions
-
- Modular widths (MW): 4
Scope supply
-
- KNX connection and junction terminal included the scope of
supply.
-
- Logical linking function for each output. 140 µF
-
- Light bulbs: 2500 W
-
- halogen lamps: 2500 W
-
- Wound transformer: 1200 VA
-
- Gira Tronic transformer: 1500 W
-
- Fluorescent lamps,
uncompensated:
2500 VA
-
- Fluorescent lamps, duo-
circuit:
2300 VA
-
- Fluorescent lamps, parallel-
compensated:
1300 VA
-
- Mercury-vapour lamps,
uncompensated:
2000 W
-
- Mercury-vapour lamps,
parallel-compensated:
2000 W
Connections: max.
-
- Memory function for light scenes