1.1. the protective
conductor separate conductor, that is, does not form part cable this example
and not enclosed wiring system Example the cross-section the protective
conductor must not less than 2.2.
Example 2
A supply feeds domestic immersion heater wired 2.
From Table 3.4s.5mm2
PVC insulated copper cable
and incorporates 1. Establish calculation that the CPC adequate size meet the
requirements Regulation 543.3 when the
protective device 30A semi-enclosed fuse.
I
V
Z
Maximum fault current (A)
A
s
∴
230
1 15
200
.
t Maximum operating time the protective device for circuit not exceeding 32A 0.2.4s
from Regulation 411.5 mm2
CPC acceptable since this the nearest standard-size conductor above the
minimum cross-sectional area 1.
So, this case the table states that 90A will trip 15A semi-enclosed fuse 0.2A can seen that current about 90A will trip the 15A fuse 0.3). The characteristics the protective device are given IEE
Regulation Table 3.
A 1.Overcurrent, short circuit and earth fault protection
251
as 1.
∴ I
t
k
S
I t
k
90
0 4
115 3
2
2
A
s
(from Table )
(mm (from Regul
.
k 115 (from Table 54.
For final circuits less than 32A the maximum operating time the protective device 0. From Fig. 12.
.3.5mm CPC meets the requirements Regulation 543. Verify that the 1.4s.1.5(b) you can see that the time taken clear fault of
200A about 0.3)
( s
mm
S
90 4
115
0 49
2
2
.
a
ation 543.
.3.4s. The
small insert Table the top right Table 3.5mm2
where mechanical protection provided
or 4.0 mm2
where mechanical protection not provided order comply with Regulation
544.
The CPC the cable greater than 0.3. The circuit correctly protected with 15A semi-enclosed
fuse 3036.4s.49mm2
and therefore suitable.15Ω.
.5 mm2
CPC.2 the IEE Regulations gives the value the
prospective fault current required operate the device within the various disconnection
times given.2.
.
S
I t
k
S
2
2
2
2
200 4
115
1 10
(mm )
( s
mm
.2A.10 mm2
found calculation