From Table 3.2 the IEE Regulations gives the value the
prospective fault current required operate the device within the various disconnection
times given.2.3.1.2.
A 1.
The CPC the cable greater than 0. The characteristics the protective device are given IEE
Regulation Table 3.5mm CPC meets the requirements Regulation 543.
S
I t
k
S
2
2
2
2
200 4
115
1 10
(mm )
( s
mm
.4s.5 mm2
CPC acceptable since this the nearest standard-size conductor above the
minimum cross-sectional area 1.2A.
k 115 (from Table 54.3).
For final circuits less than 32A the maximum operating time the protective device 0.
.
a
ation 543.
Example 2
A supply feeds domestic immersion heater wired 2.2.5mm2
PVC insulated copper cable
and incorporates 1. The
small insert Table the top right Table 3.
So, this case the table states that 90A will trip 15A semi-enclosed fuse 0.4s.4s.0 mm2
where mechanical protection not provided order comply with Regulation
544.2A can seen that current about 90A will trip the 15A fuse 0.5(b) you can see that the time taken clear fault of
200A about 0. Verify that the 1.
.
. Establish calculation that the CPC adequate size meet the
requirements Regulation 543. The circuit correctly protected with 15A semi-enclosed
fuse 3036.
t Maximum operating time the protective device for circuit not exceeding 32A 0.1.
I
V
Z
Maximum fault current (A)
A
s
∴
230
1 15
200
. From Fig.5mm2
where mechanical protection provided
or 4. the protective
conductor separate conductor, that is, does not form part cable this example
and not enclosed wiring system Example the cross-section the protective
conductor must not less than 2.
.10 mm2
found calculation.4s.49mm2
and therefore suitable.3.3)
( s
mm
S
90 4
115
0 49
2
2
.3 when the
protective device 30A semi-enclosed fuse.1.3. 12.4s
from Regulation 411.Overcurrent, short circuit and earth fault protection
251
as 1.5 mm2
CPC.
∴ I
t
k
S
I t
k
90
0 4
115 3
2
2
A
s
(from Table )
(mm (from Regul
.15Ω