Basic Electrical Installation Work

| Kategorie: Kniha  |

Strana 261 z 399

Jak získat tento dokument?






Poznámky redaktora
However, where the conductor cross-section does not comply with this table, then the formula given Regulation 543.4 of the IEE Regulations). Where line and protective con- ductors are made from the same material, Table 54.5mm single PVC copper cables a plastic conduit with separate 1.4s disconnection (Ω) 7. The circuit earth fault loop impedance less than this value and therefore the protective device will operate within the required disconnection time 0.4s.7 the IEE Regulations, there need carry out further checks.5 CPC.84 1.15 0.Basic Electrical Installation Work 250 The maximum permitted value given Table the Site Guide for 20A MCB protecting socket outlet 2.92 .44 1. Protective conductor size The CPC forms integral part the total earth fault loop impedance, it is necessary check that the cross-section this conductor adequate.2 Maximum Earth Fault Loop Impedance MCB Type Maximum Measured Earth Fault Loop Impedance (Ω) When Overcurrent Protective Device MCB Type 60898 MCB rating (A) 6 50 For 0. If the cross-section the CPC complies with Table 54. Example 1 A 230 ring main circuit socket outlets wired 2.3 must used: S I t k 2 2 (mm ) where S cross-sectional area mm2 I value maximum fault current amperes t operating time the protective device k factor for the particular protective conductor (see Tables 54.7 tells that: ● for line conductors equal less than 16mm2 , the protective con- ductor should equal the line conductor; ● for line conductors greater than 16mm2 but less than 35mm2 , the protective conductor should have cross-sectional area of 16mm2 ; ● for line conductors greater than 35mm2 , the protective conductor should half the size the line conductor.2 54.2.3 1.87 2. earth fault loop impedance test identifies Zs Table 12.3Ω shown Table 12.67 4.6 2.1