Jak získat tento dokument?






Poznámky redaktora
Electrical installations and wiring systems 305 Trap provides inspection access under floorboards to joint box Floorboards Cables passing through holes drilled joists Plaster finish wall Metal switch box PVC cable run down wall and buried plaster, covered with channel mechanical protection is required Plasterboard finish ceiling Wall FIGURE 14. Maximum depth notch should 0. Holes the same joist should least 3 diameters apart.1 and 0. Floor joists Steel conduit Greater than 50mm Insulated and sheathed cable Notes: FIGURE 14. Notches top zone between 0.22 Permitted cable routes.25 span.25 joist depth. .23 Correct installation cables floor joists.125 joist depth. 1. Protection required unless cable depth greater than 50mm No protection required 150mm 150mm Wall Wall Wall No protection required Accessory boxes FIGURE 14. 2.4 span.25 and 0. Maximum diameter hole should 0. 5. Holes centre line zone between 0. 4.21 A concealed PVC sheathed wiring system. 3