Basic Electrical Installation Work

| Kategorie: Kniha  |

Strana 313 z 399

Jak získat tento dokument?






Poznámky redaktora
5 30 13A socket outlets (Ring circuit) 2.2.0 35 Cooker (oven and hob) 6. V/Am V Since this less than the maximum permissible value for lighting circuit 6.5 30 13A socket outlets (Radial circuit) 2.9 10mm cable satisfies the current and drop voltage requirements when the circuit protected by an MCB. were able route the cable under the floor, clipped direct conduit or trunking wall, may able use 6mm cable for this load.5 30 Storage radiator 2.4mV. Compare the values column with those column When the cable clipped direct wall surface the current rating higher because the cable cooler.9V ● for other uses 11.0 40 Fixed lighting 1. Final circuits are fed from consumer unit, having Type B, MCB protection and wired PVC insulated and sheathed cables with cop- per conductors having grey thermoplastic PVC outer sheath white .5V IEE Regulation 525 and Appendix 12.5 30 Cooker (oven only) 2.Basic Electrical Installation Work 302 Now test for volt drop: from the table shown Table 14.3 the volt drop per ampere per metre for 10mm cable 4. This cable run loft that gets hot summer and has thermal insulation touching one side the cable.4 gives guide cable size. In this table, assuming standard 230V domestic installation, hav- ing sheathed earth PME supply terminated 100A HBC fuse the mains position.4 Cable Size for Standard Domestic Circuits Type final circuit Cable size (twin and earth) MCB rating, Type (A) Maximum floor area covered by circuit (m2 ) Maximum length of cable run (m) Fixed lighting 1. If you are unsure the standard fuse and MCB rating protective devices, you can refer to Fig. Cable size for standard domestic circuits Appendix the IEE Regulations (BS: 7671) and Appendix the IEE On Site Guide contain tables for determining the current carrying capacities of conductors which looked the last section. These are some the decisions which the electrical contractor must make when designing installation which meets the requirements the customer and the IEE Regulations. You can see how the current carrying capacity cable varies with the installed method looking Table 4.4 Appendix the IEE Regulations. Table 14.5 60 Immersion heater 2.5 100 90 13A socket outlets (Ring circuit) 4.6kw) 40 Key Facts Volt drop Maximum permissible volt drop on 230V supplies: ● for lighting 6. the alternative route was longer, you would need test for volt drop before choosing the cable.5kw) 6.0 40 Shower (up 7.2. must, therefore, use installed reference method of Table 4.0 40 Shower (up 9. 3. However, for standard domestic circuits, Table 14. the volt drop for this cable length and load equal to: 4 06 3