Basic Electrical Installation Work

| Kategorie: Kniha  |

Strana 302 z 399

Jak získat tento dokument?






Poznámky redaktora
5mm2 PVC cable 4 mm2 PVC cable etc. Ring circuits Ring circuits are very similar radial circuits that each socket outlet is fed from the previous one, but ring circuits the last socket wired back to the source supply.12 Block diagram radial circuits.5mm2 PVC cable FIGURE 14. 30 or 32A 30mA Fuse or MCB RCD Maximum floor area 100m2 2.Electrical installations and wiring systems 291 Maximum floor area 75m2 Maximum floor area 50m2 2. The circuit details are given Appendix the IEE Regulations but may also expressed the block diagram given Fig.13 Block diagram ring circuits. Each ring final circuit conductor must looped into every socket outlet joint box which forms the ring and must elec- trically continuous throughout its length. The number permitted socket outlets unlimited but each ring circuit must not cover more than 100m2 of floor area. Fuse MCB Fuse MCB 30 32A 20A 30mA 30mA RCD RCD FIGURE 14.13. etc. Ring and radial circuits may used for domestic other premises where the maximum demand the current-using equipment estimated not to exceed the rating the protective devices for the chosen circuit. 14. . is because the maximum demand current-using equipment kitchens may exceed the rating the circuit cable and protection devices