Basic Electrical Installation Work

| Kategorie: Kniha  |

Strana 255 z 399

Jak získat tento dokument?






Poznámky redaktora
2 provides equation for calculating the maximum operating time the protective device to prevent the permitted conductor temperature rise being exceeded as follows: t k S I 2 2 2 (s) where t duration time seconds S cross-sectional area conductor square millimetres I short-circuit rms current amperes k constant dependent upon the conductor metal and type insula- tion (see Table 43A the IEE Regulations).5. reduction may occur because change the size type conductor because of change the method installation change the environmental conditions. .Basic Electrical Installation Work 244 MCB Type 60898 will trip instantly between five and ten times its rated current. However, this condition is not met there some doubt, must verified that fault currents will be interrupted quickly before they can cause dangerously high tempera- ture rise the circuit conductors. Installing overcurrent protective devices The general principle followed that protective device must be placed point where reduction occurs the current carrying capac- ity the circuit conductors (IEE Regulations 433. This because the cable rating and the overload rating the device are compatible. suitable for welding and X-ray machines where large inrush currents may occur. The IEE Regulations permit assume that where overload protec- tive device also intended provide short-circuit protection, and has a rated breaking capacity greater than the prospective short-circuit current at the point its installation, the conductors the load side the pro- tective device are considered adequately protected against short-cir- cuit currents without further proof. Regulation 434.2). Fault protection The overcurrent protection device protecting circuits not exceeding 32A shall have disconnection time not exceeding 0. The only exceptions this rule are where overload protec- tive device opening circuit might cause greater danger than the over- load itself for example, circuit feeding overhead electromagnet a scrapyard.4s (IEE Regulations 411.2.3.2). more suitable for highly inductive commercial and industrial loads.2 and 434. MCB Type 69898 will trip instantly between and times its rated current