The government agreed January 1995 that the electricity supplies in the United Kingdom would harmonized with those the rest Europe. Source: HSE Crown copyright material reproduced with the permission the Controller HMSO and Her Majesty’s Stationery Office, Norwich. Thus the voltages used previously low-voltage supply systems 415V and 240V have become 400V for three-phase supplies and 230V for single- phase supplies. The next proposed change for the tolerance levels adjusted to 10% the declared nominal voltage (IEE Regulation, Appendix 2:14). The frequency maintained average value 50Hz over 24h that electric clocks remain accurate. The regulations are administered the Engineering Inspectorate the Electricity Division the Department Energy and will not normally con- cern the electrical contractor except that these regulations which lay down the earthing requirement the electrical supply the meter position.2 New health and safety law poster.8 Basic Electrical Installation Work These regulations impose requirements upon the regional electricity com- panies regarding the installation and use electric lines and equipment. . The permitted tolerances the nominal voltage have also been changed from 10% and 6%. FIGURE 1. The regional electricity companies must declare the supply voltage and maintain its value between prescribed limits tolerances. This gives voltage range of 216–253V for nominal voltage 230V and 376–440V for nominal sup- ply voltage 400V