13 Flowchart for secure isolation procedure. All the off-cuts conduit, trunk- ing and tray also into the skip. environment produces? Well, all the packaging material for electrical fit- tings and accessories usually goes into either your employer’s skip the skip site designated for that purpose. . fact, most the general site debris will probably into the skip and the waste disposal company will take the skip contents designated local council land fill area for safe disposal.Safe systems working 173 Select approved test lamp or voltage indicating device Verify that the device is functioning correctly a known supply proving unit Satisfactory? Locate and identify circuit or equipment worked upon Is the circuit equipment in service? Identify means isolation Ensure isolation circuit or equipment by – switching off – withdrawing fuses – locking off isolating switches or MCBs Verify that the circuit or equipment worked upon is dead using voltage indicating device testing between Phase and Earth Phase and Neutral Neutral and Earth Satisfactory? Recheck that the voltage indicating device functioning correctly known supply or proving unit Fit warning labels Satisfactory? DEAD Discover why with care and through the procedure again Replace repair and through the procedure again Begin work NO Replace repair Establish where and why it was de-energised NO YES NO LIVE YES YES FIGURE 8