Poznámky redaktora
1=No, 2=2, 3=3 1
63 Write Start Rampl 1st sequence, time for start ramp -120 Sec 10
64 Write Init Voltl 1st sequence, initial voltage for start ramp 30
65 Write Curr Liml 1st sequence, current limit 70= 2,0 7,0 xIe 4
66 Write 1st Set 1st sequence, motor rated current 3000 (*) Amp Individual
67 Write Start Ramp2 2nd sequence, time for start ramp -120 Sec 10
68 Write Init Volt2 2nd sequence, initial voltage for start ramp 30
69 Write Curr Lim2 2nd sequence, current limit 2,0 7,0 xIe 40
70 Write 2nd Set 2nd sequence, motor rated current 3000 (*) Amp Individual
71 Write Start Ramp3 3rd sequence, time for start ramp -120 Sec 10
72 Write Init Volt3 3rd sequence, initial voltage for start ramp 30
73 Write Curr Lim3 3rd sequence, current limit 2,0 7,0 xIe 40
74 Write 3rd SetIe 3rd sequence, motor rated current 3000 (*) Amp Individual
75 Read Language Language use display
1=US/UK, 2=FI, 3=SE,
4=PT, 5=NL, 6=IT,
7=FR, 8=ES, 9=DE,
10=CN, 11=RU, 12=TR Individual
76 Read Dummy Spare parameter 0
77 Read LCD Auto Off Time for display automatic turn off 255 Minutes 15
78 Read Password Password for display 0=No, 255=1- 255 1
79 Read Date Type Type date presentation 0=ISO 1=CE 2=US 0
80 Read Date Year Year 2001 2060 Individual
81 Read Date Month Month Individual
82 Read Date Day Day Individual
83 Read Time Hour Hour Individual
1SFC132021M0201. 0
56 Write Event K5
Different events include for signalling with
K5 “Event” selected
0 65535, Bit mask see
separate description. Type operation for frequency fault 0=Stop-M, 1=Stop-A 0
47 Write Temp Op
Type operation for heat sink over
temperature fault 0=Stop-M, 1=Stop-A 0
48 Write SCR Op
Type operation for thyristor short circuit
fault 0=Stop-M, 1=Stop-A 0
49 Read In0 Function programmable input In0
0=None, 1=Reset,
2=Enable, 3=Jog,
4=DOL-on, 5=Start2,
6=FB-Dis 1
50 Read In1 Function programmable input In1
0=None, 1=Reset,
2=Enable, 3=Jog,
4=DOL-on, 5=Start2,
6=FB-Dis 1
51 Write Relay Function programmable relay output 0=Run, 1=TOR, 2=Event 0
52 Write Relay Function programmable relay output 0=Run, 1=TOR, 2=Event 1
53 Write Relay Function programmable relay output 0=Run, 1=TOR, 2=Event 2
54 Write Outp Function programmable software output 0=Run, 1=TOR, 2=Event 2
55 Write Event K4
Different events include for signalling with
K4 “Event” selected
0 65535, Bit mask see
separate description. 7
58 Write Event V7
Different events include for signalling with
V7 “Event” selected
0 65535, Bit mask see
separate description.Type Parameter Description Range Unit Default
41 Write Warn Overload warning 0=No, 1=Yes 0
42 Write Lev Trip level for overload warning 90
43 Write
Warn SCR
OL Thyristor overload warning 0=No, 1=Yes 0
44 Write Loss Type operation for phase loss fault 0=Stop-M, 1=Stop-A 0
45 Write Fault Type operation for fieldbus fault 0=Stop-M, 1=Stop-A 0
46 Write Freq Op. 0
57 Write Event K6
Different events include for signalling with
K6 “Event” selected
0 65535, Bit mask see
separate description. 7
59 Read Fieldb Ctrl Control the softstarter with fieldbus 0=No, 1=Yes 0
60 Read Fieldb Type Type fieldbus 0=AS-Int, 1=Other 1
61 Read Fieldb Addr Fieldbus address 1000 0
62 Write Seq Number sequences for sequence start