Poznámky redaktora
2,0 7,0 xIe 40
8 Write Kick Start Selection Kick start 0=No, 1=Yes 0
9 Write Kick Level Level Kick start selected 100 50
10 Write Kick Time Time for Kick start selected 0,1 1,5 Sec 2
11 Write Start Range Selectable range for start ramp 0=1-30, 1=1-120 Sec 0
12 Write Stop Range Selectable range for stop ramp 0=1-30, 1=1-120 Sec 0
13 Write Overload Overload protection 0=No, 1=Normal, 2=Dual 1
14 Write Class Overload Class
0=10A, 1=10, 20,
3= 1
15 Write Class Overload Class, Dual type, Start Class
0=10A, 1=10, 20,
3= 1
16 Write Class Overload Class, Dual type, Run Class
0=10A, 1=10, 20,
3= 1
17 Write Type operation for overload protection
0=Stop-M, 1=Stop-A,
2= Ind 0
18 Write Locked Rotor Locked rotor protection 0=No, 1=Yes 0
19 Write Lock Lev Trip level for locked rotor protection 0,5 8,0 xIe 40
20 Write Lock Time Trip time for locked rotor protection 100 0,2 10,0 Sec 10
21 Write Lock Type operation for locked rotor protection
0=Stop-M, 1=Stop-A,
2= Ind 0
22 Write Underload Underload protection No, Yes 0
23 Write Underl Lev Trip level for Underload protection 0,4 0,8 xIe 5
24 Write Underl Time Trip time for Underload protection Sec 10
25 Write Underl Type operation for Underload protection
0=Stop-M, 1=Stop-A,
2= Ind 0
26 Write Phase Imb Phase imbalance protection No, Yes 0
27 Write Imb Lev Trip level for phase imbalance protection 80
28 Write Imb Op
Type operation for phase imbalance
protection
0=Stop-M, 1=Stop-A,
2= Ind 0
29 Write High High current protection No, Yes 0
30 Write High Type operation for high current protection
0=Stop-M, 1=Stop-A,
2= Ind 0
31 Write Phase Rev Phase reversal protection No, Yes 0
32 Write Rev Op
Type operation for phase reversal
protection
0=Stop-M, 1=Stop-A,
2= Ind 0
33 Write PTC PTC protection No, Yes 0
34 Write PTC Type operation for PTC protection
0=Stop-M, 1=Stop-A,
2= Ind 0
35 Write Ext ByPass External By-pass contactor used 0=No, 1=Yes 0
36 Read Dummy Spare parameter 0
37 Write Warn I=High High current warning 0=No, 1=Yes 0
38 Write I=H Lev Trip level for high current warning 0,5 5,0 xIe 12
39 Write Warn I=Low Low current warning 0=No, 1=Yes 0
40 Write I=L Lev Trip level for low current warning 0,4 1,0 xIe 8
1SFC132021M0201.
Parameters where said Type Read, can not read from the PLC (Not possible with Modbus)
No Type Parameter Description Range Unit Default
1 Write Setting Setting current 3000 (*) Amp Individual
2 Write Start Ramp Time for start ramp 120 Sec 10
3 Write Stop Ramp Time for stop ramp 120 Sec 0
4 Write Init Volt Initial voltage for start ramp 30
5 Write End Volt End voltage for stop ramp 30
6 Write Step Down
Voltage value which the softstarter shall
step down stop and where shall
commence the stop ramp.Parameters -
For this implementation all parameter values (both binary and analogue) are represented bits. 100 100
7 Write Current Lim Level the current limit