Poznámky redaktora
Each channel consists two bytes with an error code and the parameter number that caused the error. All analogue data will represented bit values. Channel Parameter No 13 Diagn. 12 Diagn. Diagnostic inputs There are channels available for fieldbus related diagnostic messages. Motor temp. Error Codes: Parameter Value out range 2 Invalid parameter No 3 Write parameter when fieldbus control isn’t enabled Word input data area Diagnostic input word Error Code Parameter No. Word input data area Analogue input word Data Representation 3 Phase current Value =1000 1000A 4 Phase current Value =1000 1000A 5 Phase current Value =1000 1000A 6 Max phase current Value =1000 1000A 7 Measured frequency Value =100 100Hz 8 Output voltage Value =100 100% 9 Calc. Channel Parameter No 1SFC132012M0201. Channel Parameter No 14 Diagn. Channel Error Code Diagn.Analogue input telegram To PLC from Softstarter. Channel Error Code Diagn. Value =100 100% 10 Counted Starts Value =100 10000 times 11 Run Time Value =100 1000 hours *) Phase current L1, and indicates the current through the softstarter while the Max phase current always the line current. Channel Error Code Diagn. The latest error stored channel the second latest channel and the third latest channel The binary output bit “reset active diagnostics” used clear the diagnostic area