The baud rate mapped the slave address, e.Example for set up.
2.
Send configuration data the softstarter (Number I/O number parameters, etc. FBP technical description 2CDC194001D0201. Therefore the master and the slave will have the communication parameters:
1 start bit, stop bit, data bit, even parity, 19200 baud
Data exchange with the Modbus RTU master
Step1
Without receiving the configuration data the softstarter not responding the request
telegrams the Master (LED the FBP blinking).).
After the configuration the softstarter will regular Modbus slave (LED off) and will
respond the polling telegrams the master. Set the communication parameters.01 and Ver 03.
This document describes application example between Modbus RTU
master PLC CPU, PC, etc.
Softstarters PST installation and commissioning manual SFC132003M0201, Jan 2005
Softstarter software version: Ver 03.
Step 2
Now the master can send different Modbus telegrams order exchange data with the
Softstarter. and the ABB softstarter PST equipped with
a modbus fiedbus plug. Set the softstarter address and field bus communication.05.
In this particular example following documents has been used:
Modbus RTU FBP FielBusPlug MRP21.
1SFC132021M0201 10
.00
For other versions software RED marked figures this example will change
Softstarter settings
1.
Softstarter PST Modbus RTU communication.
Change the default address 248 the softstarter with the keypad (Fieldb Addr)
and enable the fieldbus communication Fieldb Ctrl=Yes ). the baud rate the slave is
19200. Please always use the actual softstarter and FBP manuals.g.04.
The communication parameters are: Start bit, Data bits, the Parity will adapted the
master