Type Parameter Description Range Unit
93 Read SOP1 Thyristor Parameter 1
<N
1
<o
94 Read SOP2 Thyristor Parameter 0,05 20,00
95 Read SOP3 Thyristor Parameter 0,011 1,200
96 Read SOP4 Thyristor Parameter 1,0 20,0
97 Write Closed Type operation for by-pass doesn’t open Stop-M, Stop-A
98 Write Open Type operation for by-pass doesn’t close Stop-M, Stop-A
99 Read Dummy Spare parameter 0
100 Read FCODE1 Factory code 0-10
101 Read FCODE2 Factory code 0-10
102 Read FCODE3 Factory code 0-10
103 Read FCODE4 Factory code 0-10
104 Read FCODE5 Factory code 0-100
105 Read FCODE6 Factory code 0-100
106 Read PST(B) PST(B) size 1-2500 Amp
107 Read FCODE7 Factory code Yes, No
108 Read FCODE8 Factory code Yes, No
109 Read FCODE9 Factory code Yes, No
110 Read FCODE10 Factory code 0-25
*) For the purpose having one common GSD-file for the whole range softstarters “Setting Ie”,
“1st Set Ie”, “2nd Set Ie” and “3rd Set Ie” have the range 3000 Amp.
16 Bit Mask for
Events Relay
outputs
Bit Overload
Bit Fault
Bit High I
Bit SCR OL
Bit Locked Rotor
Bit Underload
Bit Phase Imb
Bit PTC
Bit Phase Rev
Bit Warn OL
Bit Warn SCR OL
Bit Warn I=High
Bit Warn I=Low
Bit Shunt Fault
Bit Spare
Bit Spare
1SFC132013M0201. The softstarter itself will have much
more narrow range defined its rated current and only values within the softstarters range will accepted, other
values will skipped