• All 2007 Series terminal blocks are rated A/500 V
(IEC) and 300 (UL).
• Combines high functionality with compact design (99. Connecting measurement device via
test socket the meter side can only performed
once circuit disconnection complete (disconnect link in
measuring position III).6
mm long and wide).
Insert insulated, touch-proof circuit jumpers into jumper
slot.
First, the current transformer shorted via disconnect
link and circuit jumper (insert jumper, move disconnect link
from operating position shorting position II, activate
shorting path).98
Jumper slot
Conductor entry
Test socket
Test socket
Circuit jumper
Meter side
Transformer side
Disconnect link in
operating position I
Jumper slot
Conductor entry
Jumper slot
Conductor entry
Test socket
Test socket
Circuit jumper
Meter side
Transformer side
Disconnect link in
measuring position III
(test current measurement)
Jumper slot
Conductor entry
Jumper slot
Conductor entry
Test socket
Test socket
Circuit jumper
Meter side
Transformer side
Disconnect link in
shorting position II
Jumper slot
Conductor entry
www.
• Touch-proof test sockets for test plugs on
transformer and meter side.
• With terminal block width mm, the maximum
cross-section for solid and fine-stranded conductors
is mm² AWG) and mm² (10 AWG) for ferruled
conductors.
Advantages:
• Top-of-unit circuit jumper slot for shorting path activa-
tion
• Disconnect link provides intuitive and easy operation, as
well exact switching status indication.com
Rail-Mount Terminal Blocks, TOPJOB® S
Rail-Mount Terminal Blocks, TOPJOB® S
WAGO’s TOPJOB® Current Transformer (Disconnect/
Test) Terminal Block (2007-8821) designed for current
transformer circuits.
TOPJOB® S
Current Transformer Terminal Blocks, 2007-8821 (Orange Disconnect Link)
.wago.
Preparing shorting path for the current transformer
circuits.
• Compatible with through and ground conductor terminal
blocks having the same profile.
Using locking covers profiles for adjacent terminal
blocks allows disconnect links operated simultane-
ously