Terminal blocks Klippon Connect

| Kategorie: Katalog  |

Vydal: Weidmüller, s.r.o.

Strana 762 z 838

Jak získat tento dokument?






Poznámky redaktora
Ex i Ex ec ATEX C.Principles for the use terminal blocks Ex-areas Requirements for terminal blocks for type protection Equipment protection Intrinsic safety i For applications with type protection equipment intrinsic safety separate approval required for terminal blocks. For example, all disconnectable elements must have release force greater than N or 100 times their own weight prevent unintentional opening. this case, increased requirements apply the terminal blocks and their functional units.36 3029140000 Installation C Standards and industries . addition the approved terminal blocks, other standard terminal blocks can also used, whereby the following more stringent spacing requirements apply the area: • Between conductor entries adjacent terminals • Between conductor entries and grounded metal parts • Increased requirements for clearances due solid insulation Requirements for terminal blocks for type protection ec When test disconnect terminal blocks fuse terminal blocks are used, they must have approval for the type protection for equipment protection increased safety ec. Further approvals and guidelines for the explosion protected areas Other national and international approvals and directives are based the IECEx approval. For example, ATEX for the European market, CCC for the Chinese market, for the South Korean market EAC for the Eurasian Economic Union, which includes Russia, Belarus, Kazakhstan, Kyrgyzstan and Armenia