This does mean risk ground loops forming. The illustration shows the resulting pattern. However cable shields and steel conduits should grounded both sides, despite the risk, todays EMC regulations require this.262 3029140000 B .Application range Schematic representation Different contacting possibilities the cable screen Shielding both sides One sided shielding To protect against possible interference effects alternating magnetic field bilateral Hang unavoidable. If shielding used protect against electrical fields, it is advisable ground one side only. The insulation the conductor first separated over the circumference. The insulation can cut any point the conductor. Shielding and earthing Shield clamping saddle B. Shields analogue signal conductors should, for example, connected one end. In the same way, shields two-sided signal conductors should be grounded both sides. Then the tool pulled lengthwise over the conductor and the insulation cut off. Stripping tool for shielded cables With the Weidmueller stripping tool, very easy to disconnect the insulation conductor and then apply the shield. Finally, the insulation cut the other end over the circumference